Showing 1–12 of 15 results
-
24 KV-OC
24 KV-OC Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â :Â Compacted round stranded hard drawn aluminium wires
                                           : 35 mm2 up to 185 mm2
                                           : Cross-linked Polyethylene (XLPE)
                                           : Maximum conductor temperature 90 °C
                                           : Circuit voltage not exceeding 24 KV
                                           : 11 KV (Testing Voltage)
-
33KV-OC
33 KV-OC
Conductor : Compacted round stranded hard drawn aluminium wires
: Single-core : Size 35 mm² up to 185 mm²Insulation : Black Cross-linked polyethylene (XLPE) Core indentification : Color : Black Classification : Maximum conductor temperature 90°C
: Circuit voltage not exceeding 33,000 VoltsTesting voltage : 17,000 Volts Reference standard : ICEA S-66-524, ICEA S-93-639 -
60227 IEC 01 THW
Non-Sheathed Cables for Fixed Wiring
Building wiring for installation on insulator or in raceway, dry location.
-
60227 IEC 02 THW (F)
Flexible CablesÂ
60227 IEC 02 THW (F) Â Â Â Â :Â Flexible annealed copper wire
                    : 1.5 mm2 up to 240 mm2
                    : Polyvinyl Chloride (PVC/C)
                    : Any Color (Single Core)
                    : Maximum conductor temperature 70 °C
                    : Circuit Voltage not exceeding 450/750 V
                    : 2500 V (Testing Voltage)
-
60227 IEC 10 NYY
Sheathed Cables for Fixed Wiring
60227 IEC 10 NYYÂ Â Â Â Â Â Â Â Â Â Â Â :Â Solid and stranded annealed copper
                                       : 1.5 mm2 up to 10 mm2 (Solid)
                                       : 1.5 mm2 up to 35 mm2 (Stranded)
                                       : Polyvinyl chloride (PVC/C)
                                       : 2 Cores to 5 Cores
                                       : Black Polyvinyl Chloride (Inner Sheath) (PVC)
                                       : Black Polyvinyl Chloride (Outer Sheath) (PVC/ST4)
                                       : Maximum conductor temperature 70 °C
                                       : Circuit Voltage not exceeding 300/500 V
                                       : 2000 V (Testing Voltage)
-
60227 IEC 53 VCT
Flexible Cables
For household appliances, electrical equipment and electrical illumination.
-
60227 IEC 53 VCT-G
Flexible Cables
 For household appliances, electrical equipment and electrical illumination.
-
60227 IEC 56
60227 IEC 56
300/300 V 90°C FLEXIBLE CONDUCTOR PVC INSULATED AND SHEATHED, ROUND TYPE
Conductor : Flexible annealed copper wires
Size 0.5 mm ² and 0.75 mm²Insulation : Polyvinyl chloride (PVC/E) Core identification : 2 Cores : Blue and Brown
: 3 Cores : Brown, black and greyor Blue, Brown and Green/YellowOuter sheath : Black polyvinyl chloride (PVC/ST10) Classification : Maximum conductor temperature 90°C
: Circuit voltage not exceeding 300/300 Volts
300 Volts between Line-to-Earth
300 Volts between Line-to-LineTesting voltage : 2,000 Volts Reference standard : TIS 11 Part 5-2553, Table 11 -
FD-0.6/1KV-AL-CV
FD-0.6/1KV-AL-CV
Conductor : Concentric stranded and hard drawn alminium
: Single-core : Size 10 mm² up to 500 mm²
: Multi-core : Size 10 mm² up to 400 mm²Insulation : Cross-linked Polyethylene (XLPE) Core identification : Single-core : Natural (Translucent)
: 2 Core : Blue and Brown
: 3 Core : Brown, Black and Grey
: 4 Core : Blue, Brown, Black and Grey
: Other colors are available on customer requestSheath : Black Flame retardant polyvinyl chloride (PVC/ST2) Classification : Maximum conductor temperature 90°C
: Circuit voltage not exceeding 1,200 VoltsRated voltage : 600 Volts between Line-to-Earth
: 1,000 Volts between Line-to-LineTesting voltage : 3,500 Volts Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1 -
FD-0.6/1KV-AL-CV-SWA
FD-0.6/1 KV-CV-SWA
Conductor : Concentric stranded and hard drawn aluminium
: Size 10 mm² up to 400 mm² (Multi Core)Insulation : Cross-linked Polyethylene (XLPE) Core identification : Compound color or color tape
: 2 Core : Blue and Brown
: 3 Core : Brown, Black and Grey
: 4 Core : Blue, Brown, Black and Grey
: Other colors are available on customer requestArmor : Galvanized steel wires Sheath : Black Flame retardant polyvinyl chloride (PVC/ST2) Classification : Maximum conductor temperature 90°C
: Circuit voltage not exceeding 1,200 Volts
: Rated voltage (U0Â /U) 0.6/1 KV
: 600 Volts between Line-to-Earth
: 1,000 Volts between Line-to-LineTesting voltage : 3,500 Volts Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
: IEC 60332-3-24 (Cat.C)